This command reports the current situation of the device:
[13:42:55] ABILIS_CPX:d d ups
RES:Ups -----------------------------------------------------------------------
       Uninterruptable_Power_Supply_device                                     
       USB-STATE:CONNECTED    UPTIME:41 days 21:09:37 (13/07/2017 14:49:33)
       POWER-SOURCE:MAIN                              BATTERY:NOT-PRESENT
       V-OUT-ALARM:NO         V-MAIN-ALARM:NO         BATTERY-LOW:N/A
       V-OUT:+12.1 V          V-MAIN:+12.0 V          V-BATT:+0.0 V           
       - Battery Charger ------------------------------------------------------
       CHARGER:ENABLED        CHARGING:NO             
       V-CHARGE:+13.9 V       I-CHARGE:+0.0 A         DUTY-CYCLE:50%
       - Manual battery test result -------------------------------------------
       TEST-ALLOWED:NO        TEST-DELAY:N/A
       LAST-RESULT:NOT-TESTED
       LAST-EXECUTION:N/A
       V-NO-LOAD:N/A          V-START:N/A             V-END:N/A    The meaning:
USB-STATEState of the UPS:
DISCONNECTED - The device is not
                connected.
CONNECTED - The device is
                connected.
UPTIMEUptime of the UPS. N/A -
            USB-STATE is
            DISCONNECTED.
POWER-SOURCEPower source:
MAIN - The main power voltage is
                present.
BATTERY - The main power voltage is
                not present.
N/A - USB-STATE is
                DISCONNECTED.
BATTERYBattery condition:
NOT-PRESENT - The battery isn't
                present.
PRESENT - The battery is
                present.
PRESENT-TESTING - The battery is
                present and under testing.
N/A - USB-STATE is
                DISCONNECTED.
V-OUT-ALARMThe output regulated voltage is out of range:
NO - The output regulated voltage is
                in the proper range.
YES - The output regulated voltage is
                outside the proper range.
N/A - USB-STATE is
                DISCONNECTED.
V-MAIN-ALARMThe main voltage is out of range
NO - The main voltage is in the
                proper range.
YES - The main voltage is outside the
                proper range.
N/A - USB-STATE is
                DISCONNECTED.
BATTERY-LOWThe battery voltage is below the threshold:
NO - The battery voltage is over the
                battery low threshold.
YES - The battery voltage is below
                the threshold.
N/A - USB-STATE is
                DISCONNECTED or BATTERY
                is NOT-PRESENT .
V-OUTOutput regulated voltage value. N/A -
            USB-STATE is
            DISCONNECTED.
V-MAINMain power source voltage. N/A -
            USB-STATE is
            DISCONNECTED.
V-BATTBattery voltage value measured when the battery charger is
            disconnected. N/A -
            USB-STATE is
            DISCONNECTED.
CHARGERCharger state:
ENABLED - The battery charger is
                enabled.
DISABLED - The battery charger is
                disabled or the external voltage is too low to charge the
                battery.
N/A - USB-STATE is
                DISCONNECTED.
CHARGINGBattery charging state:
NO - The battery is not charging: the
                battery charger is disconnected (CHARGER is
                DISABLED) or the charging current
                (I-CHARGE) is less than ~200mA.
YES - The battery is charging.
N/A - USB-STATE is
                DISCONNECTED.
V-CHARGEBattery voltage value measured when the battery charger is
            connected. N/A - USB-STATE
            is DISCONNECTED.
I-CHARGEBattery charge current. N/A -
            USB-STATE is
            DISCONNECTED.
DUTY-CYCLEBattery charging duty cycle:
0 - The battery charger is always
                disconnected.
50 - The battery charger is connected
                half of the time with a period of 4 seconds.
100 - The battery charger is
                disconnected for 0.5 seconds every 60 seconds.
N/A - USB-STATE is
                DISCONNECTED.
TEST-ALLOWEDInform if the test can be executed:
NO - It isn't possible to execute the
                test.
YES - It is possible to execute the
                test.
TESTING - Test is already
                ongoing.
N/A - USB-STATE is
                DISCONNECTED.
TEST-DELAYSeconds before the DENIED barrier is
            removed. N/A - USB-STATE is
            DISCONNECTED.
LAST-RESULTResult of the battery test:
NOT-TESTED - Test results not
                available: the test has not been executed yet.
SUCCESSFUL - The battery passed the
                test.
FAILED - The battery fail the
                test.
DENIED - It is not possible to start
                the battery test because there has been a switch to battery in
                the last 24 hours (caused by a power failure or by a battery
                test).
BATTERY-LOW - It is not possible to
                start the battery test because the battery voltage is too
                low.
BATTERY-NOT-PRESENT - It is not
                possible to start the battery test because there isn't any
                battery.
TESTING - Test is running right
                now.
N/A - USB-STATE is
                DISCONNECTED.
LAST-EXECUTIONDate and Time of last test execution. N/A
            - USB-STATE is
            DISCONNECTED.
V-NO-LOADVoltage of the battery before starting the test.
            N/A - USB-STATE is
            DISCONNECTED or LAST-RESULT
            is one of the following: NOT-TESTED,
            DENIED, BATTERY-LOW,
            BATTERY-NOT-PRESENT or
            TESTING.
V-STARTVoltage of the battery after starting the test.
            N/A - USB-STATE is
            DISCONNECTED or LAST-RESULT
            is one of the following: NOT-TESTED,
            DENIED, BATTERY-LOW,
            BATTERY-NOT-PRESENT or
            TESTING.
V-ENDVoltage of the battery when the test finish.
            N/A - USB-STATE is
            DISCONNECTED or LAST-RESULT
            is one of the following: NOT-TESTED,
            DENIED, BATTERY-LOW,
            BATTERY-NOT-PRESENT or
            TESTING.
This command can help to understand what is happening, in case of troubles:
[13:48:36] ABILIS_CPX:d s ups 
RES:Ups -----------------------------------------------------------------------
       Uninterruptable_Power_Supply_device                                     
       --- Cleared 41 days 21:08:34 ago, on 13/07/2017 at 14:50:51 ------------
       -----------|---INPUT---|--OUTPUT---|-----------|---INPUT---|--OUTPUT---|
       SW-SHUTDOWN|           |          0|V-MAIN-ALM |          0|           |
       HW-SHUTDOWN|          0|           |V-OUT-ALM  |          0|           |
       BATT-LOW   |          0|           |           |           |           |
       V-MAIN-FAIL|          0|           |LIVE       |           |    3618517|
       CHARGE-DIS |          0|           |LIVE-EXP   |          0|           |
       ------------------------------------------------------------------------With reference to the shown interval of time («Cleared 41 days 21:08:34 ago») these counters show the number of:
SW-SHUTDOWN | V_OUT_HOST_SHUTDOWN received from the UPS. | 
HW-SHUTDOWN | V_OUT_UPS_SHUTDOWN received from the UPS. | 
BATT-LOW | BATTERY LOW received from the UPS. | 
V-MAIN-FAIL | Failures of the MAIN power. | 
CHARGE-DIS | BATTERY CHARGER disconnection received from the UPS. | 
V-MAIN-ALM | V_MAIN_ALARM detected by the UPS. | 
V-OUT-ALM | V_OUT_ALARM detected by the UPS. | 
LIVE | LIVE received by the UPS. | 
LIVE-EXP | Times the LIVE has expired in the UPS. |